Наружный диаметр | Толщина изоляционного слоя, мм | ||||||
60 | 70 | 80 | 90 | 100 | 120 | 140 | |
Расход материалов, м3 | |||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
108 | 0,424 | 0,524 | 0,633 | 0,750 | 0,875 | 1,151 | - |
133 | 0,487 | 0,598 | 0,717 | 0,844 | 0,980 | 1,277 | - |
159 | 0,553 | 0,674 | 0,804 | 0,943 | 1,090 | 1,408 | 1,761 |
219 | 0,650 | 0,786 | 0,929 | 1,080 | 1,239 | 1,580 | 1,952 |
273 | 0,776 | 0,932 | 1,097 | 1,269 | 1,448 | 1,831 | 2,245 |
325 | 0,897 | 1,074 | 1,258 | 1,450 | 1,650 | 2,074 | 2,528 |
377 | 1,018 | 1,215 | 1,420 | 1,632 | 1,852 | 2,316 | 2,811 |
426 | 1,038 | 1,236 | 1,441 | 1,653 | 1,872 | 2,332 | 2,820 |
476 | 1,145 | 1,360 | 1,583 | 1,813 | 2,050 | 2,546 | 3,070 |
529 | 1,258 | 1,492 | 1,734 | 1,983 | 2,239 | 2,772 | 3,334 |
630 | 1,474 | 1,744 | 2,022 | 2,307 | 2,598 | 3,203 | 3,837 |
720 | 1,666 | 1,968 | 2,278 | 2,595 | 2,919 | 3,588 | 4,286 |
820 | 1,879 | 2,218 | 2,563 | 2,915 | 3,275 | 4,015 | 4,784 |
Плоская поверхность, 10 м2 | 0,742 | 0,865 | 0,989 | 1,112 | 1,236 | 1,483 | 1,730 |
Примечание. При расчете расходов изделий минераловатных с гофрированной структурой | |||||||
учтены коэффициенты уплотнения в соответствии со СНиП 2.04.14-88 "Тепловая изоляция | |||||||
оборудования и трубопроводов": | |||||||
а) 1,3 - для трубопроводов до Ду 150 мм включительно; | |||||||
б) 1,2 - для трубопроводов от Ду 200 мм до Ду 350 мм включительно; | |||||||
в) 1,1- для трубопроводов свыше Ду 350 мм. |
Таблица 10 - Расход плит минераловатных на битумном связующем для изоляции трубопроводов
сегментами, нарезанными из плит. Норма на 10 м трубопровода
Наружный диаметр | Толщина изоляционного слоя, мм | ||||||||||
40 | 50 | 60 | 70 | 80 | 90 | 100 | 120 | 140 | 160 | 180 | |
Расход материалов, м3 | |||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
219 | 0,386 | 0,502 | 0,624 | 0,755 | 0,892 | 1,037 | 1,190 | 1,517 | 1,875 | 2,262 | 2,679 |
273 | 0,467 | 0,602 | 0,745 | 0,895 | 1,053 | 1,218 | 1,391 | 1,759 | 2,156 | 2,584 | 3,041 |
325 | 0,545 | 0,699 | 0,862 | 1,031 | 1,208 | 1,393 | 1,585 | 1,992 | 2,428 | 2,894 | 3,390 |
377 | 0,622 | 0,796 | 0,978 | 1,167 | 1,364 | 1,568 | 1,779 | 2,224 | 2,700 | 3,204 | 3,739 |
426 | 0,695 | 0,888 | 1,088 | 1,295 | 1,510 | 1,732 | 1,962 | 2,444 | 2,955 | 3,497 | 4,068 |
476 | 0,770 | 0,981 | 1,199 | 1,425 | 1,659 | 1,900 | 2,148 | 2,667 | 3,216 | 3,795 | 4,404 |
529 | 0,849 | 1,080 | 1,318 | 1,564 | 1,817 | 2,078 | 2,346 | 2,905 | 3,493 | 4,112 | 4,760 |
630 | 1,000 | 1,268 | 1,544 | 1,828 | 2,118 | 2,417 | 2,723 | 3,357 | 4,021 | 4,714 | 5,438 |
720 | 1,134 | 1,436 | 1,745 | 2,062 | 2,387 | 2,719 | 3,058 | 3,759 | 4,490 | 5,251 | 6,042 |
820 | 1,283 | 1,622 | 1,969 | 2,324 | 2,685 | 3,055 | 3,431 | 4,207 | 5,013 | 5,848 | 6,713 |
Плоская поверхность, | 0,475 | 0,594 | 0,712 | 0,831 | 0,950 | 1,068 | 1,187 | 1,425 | 1,662 | 1,899 | 2,137 |
10 м2 | |||||||||||
Примечание. Расход плит на битумном связующем дан с учетом коэффициентов расхода: | |||||||||||
а) 1,02 - на изоляцию трубопроводов; | |||||||||||
б) 1,13 - на изготовление сегментов. | |||||||||||
Таблица 11 - Расход металла на покрытие тепловой изоляции трубопроводов. Норма на 10 м покрытия тепловой изоляции трубопровода
|